Sign in
Guest Post Guidelines for the agriculture01.com Blog
Guest Post Guidelines for the agriculture01.com Blog
Your Position: Home - Steel Structures - Multi-storey steel building
Guest Posts

Multi-storey steel building

Aug. 06, 2024

Multi-storey steel building

Multi-storey steel building

For multi-storey steel building, we have two main options:

If you are looking for more details, kindly visit our website.

  • the stiffness is provided by moment resistant frame or
  • the stiffness is provided by some kind of bracing system (and the structure uses simple connections).

There are also other approaches like for example partially restrained frames but these are complicated compared to the aboves.

This studied building has footprint as depicted above. The height is 9 floors, 4.5 m each. The columns are assumed to be simple supported at their footings. Only the middle frame will be taken and analysed. The main beam within each floor transmitts load from the secondary beams, which support slab (the secondary beam load will appear as a single force in the middle of the span of the main beam).

Wind load

While for small buildings wind load might be almost negligible and it is gravity load what determines sections, for tall buildings wind load is main component for analysis. Wind load increases with altitude and since it acts on a great arm (height of the building) it works with leverage.

For wind load the basic wind speed was taken as 30 m/s. Characteristic speed, which is related to a topology and height was determined as

height $\boldsymbol{z}$ [m] &#;$\boldsymbol{v_{n}(z)}$ [m/s] 10 22.6 20 27.0 30 29.7 40 31.6

The maximum characteristic wind pressure from the characteristic speed and with turbulences' impact

height $\boldsymbol{z}$ [m] &#;$\boldsymbol{q_{p}(z)}$ [Pa] 10 956 20 30 40

Finally according to the shape/disposal of the building we can get load on the both front and back side. Wind load grows with height. If one side is taken as a front side (coefficient $c_{pe} = 0.8$), then wind pushes this wall while the opposite side is being sucked by the wind $(c_{pe} = -0.6)$.

height $\boldsymbol{z}$ [m] &#;$\boldsymbol{q_{w+}(z)}$ [kN/m] &#;$\boldsymbol{q_{w-}(z)}$ [kN/m] 10 765 -574 20 972 -729 30 -833 40 -910

Finally we want to convert Pascals to Newtons per meter. Since the wall&#;which is being assumed as a part for the main frame&#;has depth of 9 m, the wind load for the frame is stated as

height $\boldsymbol{z}$ [m] &#;$\boldsymbol{q_{w+}(z)}$ [kN/m] &#;$\boldsymbol{q_{w-}(z)}$ [kN/m] 10 6.9-5.2 20 8.8-6.6 30 10.0-7.5 40 10.9-8.2

Dead load

Dead load (or gravity load) is simplified to

 kN/m2   $\boldsymbol{\gamma_f}$   $\boldsymbol{w_d}$ [kN/m2]  Flooring system (slab)2.51.152.9 Equipment 0.71.250.8 Live load 3.01.253.8 $\sum$ 7.5

Since we want to process 2D frame, we have to convert the load to kN/m according to the depth of 9 m. Load is $q_d = w_d \times 9 = 67.5$ kN/m. Within one field (of 8 m) this load is transmitted in 3 places: in exterior column (2 m × 67.5 kN/m = 135 kN), interior column (270 kN) and in the middle of the beam where main beam supports the secondary beam (270 kN).

Model

Sections

Based on the observed internal forces sections are suggested. This website was helpful to propose a design since for any profile a strength in tension, compression and bending is readily available.

  • Exterior column: UPE 300×4. The built-up column 400 × 600 mm is assumed to form a new rigid section which is able to transmitt bending moments. Area of built-up section is 226 cm2, using tabled values and Steiner's theorem moment of inertia was determined as I = 69,100 cm4.
  • Interior column: UPE 400×4. The built-up column 400 × 800 mm. A = 367 cm2, I = 110,600 cm4.
  • The horizontal beam: IPE500×2: A = 232 cm2, I = 96,400 cm4
  • For the upper part of the building there is no need to use such heavy members. Exterior column for upper part: UPE200×4, 300 × 400 mm: A = 116 cm2, I = 18,700 cm4
  • Interior column for upper part: UPE270×4, 300 × 540 mm: A = 179 cm2, I = 27,840 cm4
  • The horizontal beam for upper part was chosen as IPE400×2: A = 169 cm2, I = 46,200 cm4

These are not optimum sections. But we have quite meaningful sections to start with. We have to expect different internal forces once the model is calculated with non constant stiffnesses.

Model with sections assigned: results

The internal forces are now slightly different so we should consider new values, provide slightly different sections or more efficient sections, run the next iteration, make an assessment. But for the time being and our demonstrative purpose let us accept that the sections are designed appropriately since we want to step in to read deflections.

The horizontal deflection on the top floor was found to be 0.38 m (see the above picture). The deflection from a vertical wind load is quite disturbing and it was taken only as a static load. For a case of resonance the deflections would be greater, perhaps much greater and with fatigue involved would threaten to bring a collapse. So, even if the frame could resist the load in terms of strength, the deflections would be unacceptable. The moment resistant frame is not feasible solution for tall buildings. The vertical deflection at the middle of the spans is almost 2 cm.

Yunsheng supply professional and honest service.

If moment resistant frame can not be used for tall buildings, what about third floor then? On the top of the 3rd floor the deflections observed are around 0.2 m. Even for three-storey building such displacement can not be allowed. The trick is we have to remove all floors above the 3rd floor firstly to show real displacement for three-storey building (the top's floors of the building act as a lever): vertical deflection is around 3.2 cm then.

Modified frame: braces

From the above results it is reasonable to conclude that the frame has to be equipped with braces. That improves stiffness significantly and likely gets the deflections under control.

For bracing, profiles L120x120x12 were considered. These are simply connected to the frame.

Once the frame is solved, it shows roughly 10 times smaller vertical displacement: at the top floor 4.4 cm (compare to 0.38 m on unbraced frame). According to the model, the most exposed brace has to resist 420 kN in compression. Profile L120x120x12 can transmitt 650 kN in pure compression ($\gamma_{M0} = 1$). It means that for most of the braces the angle is sufficient, only at the bottom floors section has to be adjusted to a stronger one (buckling). Besides that the frame is stiff as the whole, therefore the beams do not show excesive bending moments (as unstiffened frame does).

The logical step is to remove the moment resistant connections (of beams to columns), which are expensive and replace them by simple connections. The maximum vertical deflection of the top floor is only slightly higher then (5.6 cm). But the structure is simpler and cheaper.

Summary

The example is highly simplified and its purpose is not to make design and/or assessment. The purpose is to demonstrate the difference between moment resistant frame, which is suitable for a few-storey buildings against braced frame which uses pinned connections. The latter is cost efficient for tall buildings.


List of chapters

Multi-Storey Building

Airports

The integrated terminal buildings are designed with number of structural innovations. The key feature of airport structure is their long span roof covering with massive column spacing. The mega columns and large cantilevers make the structure unique. By using modular space frame structure supported by cantilevered columns makes the roof aesthetically good with doubly curved.

Go To Full Page

Pre-Engineered Buildings

It offers a futuristic solution for creating durable and efficient structures in cost effective manner. Apart from great flexibility of designing and minimal construction time offered by PEB&#;s, they are also preferred for their robustness and durability. Moreover, it is possible to add a wide range of structural and non structural components, which enhances their aesthetic appeal and also improve their usability.

Go To Full Page

Space Frames

Space frame is a three dimensional structure. The 3D behavior ensures optimum utilization of material. The quality of roofing is exceptional good as the deflections are almost negligible. Despite their light weight, these structures are designed to carry much heavier load and have a huge spanning capacity. Erection time is minimal as the material is pre fabricated from the factory.

Go To Full Page

Multi-Storey Buildings

Steel frames construction is a very popular structural form for multi storey buildings as it provides great flexibility. The structure has adequate strength and stiffness to resist the applied loads due to gravity and wind. The function of the structure in resisting vertical loads due to gravity and horizontal loads due to wind is generally considers separately.

Go To Full Page

Solar Energy

Coming Soon

Bulk Storage Sheds

Bulk storage sheds are large span structure to accommodate tons of coals for continuous supply to the boilers.The structures are designed with modular space frame to make it cost effective compared to other conventional structures. Catwalks, ducts and other services can be accommodated within the top and bottom chord.

Limestone Gypsum Additive Iron Ore Coal

Membrane Structures

Textile supported by steel combines the high flexibility of use of this one, from reticular arches to infinite space geometries, with a singular covering applied only with optimum conditions in order to avoid abrasion and corrosion due to contact with main bearing structure. The all season use is guaranteed by a singular system of side opening in order to obtain maximum ventilation in hot season.

Go To Full Page

Self Supporting Roofs

Self supporting roofing system makes it possible to erect a warehouse in one span without trusses, purlins and rafters. The systems are mechanically sealed which ensures better weather proofing and a hygienic and clean environment. The absence of holes, nuts, bolts, overlaps or sealants, these structures require minimal to zero maintenance making them highly cost efficient.

If you are looking for more details, kindly visit Multi-storey Steel Structure Building.

Go To Full Page

Comments

0 of 2000 characters used

All Comments (0)
Get in Touch

  |   Transportation   |   Toys & Hobbies   |   Tools   |   Timepieces, Jewelry, Eyewear   |   Textiles & Leather Products   |   Telecommunications   |   Sports & Entertainment   |   Shoes & Accessories   |   Service Equipment